Model:ROC-2313/3313 Reverse osmosis process controller
Typical applications
Integrated integration single stage reverse osmosis water making system of procedure control and conductivity measurement control
Technical data
反渗 Reverse osmosis collection points: Raw water without water protection、low-voltage protection、High voltage protection、Pure water high level protection、External control、Running reset。
Reverse osmosis control points: raw water pump、high-pressure plunger pump、inlet valve、flush valve、The conductivity of excess emissions valves。
Test project: 测试项目 : conductivity/temperature
Choose electrode: Two electrode type
display mode:3 1/2 a red LED digital display
Standard distribution extremely: 1.0cm-1 electrode
tested range: conductivity 0.0μS/cm~200.0 μS/cm temperature 0~50℃
Resolution ratio: conductivity 0.1μS/cm
temperature 0.1℃
Accuracy: conductivity ≤1.5%
temperature≤0.5℃
Temperature compensation : In 25 ℃ as a benchmark, automatic digital compensation
Working conditions: temperature:0~50℃;relative humidity:≤85%/RH
Electrical control: ON single contacts relays, dry contact (no distribution)
Contact capacity AC 230V/5A Max;AC 115V/10A Max(Resistance sex load)
Power supply AC 165V~260V 50Hz
Dimension :ROC-2313 96 mm×96 mm×130mm(H×W×D)
ROC-3313 130 mm×180 mm×60mm(H×W×D)
Slot dimension: ROC-2313 91 mm×91mm(H×W)
ROC-3313 122 mm×172mm(H×W)
Installation: panel mounted
|